Integrity
Management on TAPS
Pump Station Pressure Relief System
In all of the pump stations, piping pressure relief systems
have been designed to keep existing and surge pressures from
exceeding 110% of the pipe’s internal design pressure. Pressure
relief for each pump station is provided by connecting the
suction and discharge relief valve piping manifolds to the crude
tanks. Connection to the tanks varies for each pump station.
Each station has either two or three hydraulically operated
pressure relief valves on both the suction and discharge side of
the station, except Pump Station 4, which has only suction
relief valves.

|
 |